Communication between Fronius Symo GEN24 10.0 Plus and Fronius Smart meter TS 65A-3

Every value is stored in two registers with 16 bit each. These two registers will be combined to one 32 bit value. The low word is stored at the lower address. This 32 bit value will be interpreded as singned 32 bit integer.

Read holding register for device ID 1 , Start address = 258 Quantity = 16

Every second

Reg Description Unit
258..259Voltage0.1 V
260..261Voltage Phase Phase0.1 V
262..263PowerReal_P_Sum0.1 W
264..265PowerApparent_S_Sum0.1 VA
266..267PowerReactive_Q_Sum0.1 var
268..269PowerFactor_Sum0.001 °
270..271PowerReal_P_Sum OR PowerFactor_Sum OR Current_AC_Sum???
272..273Frequency0.1 Hz

Read holding register for device ID 1 , Start address = 286 Quantity = 42

Every second

Reg Description Unit
Phase 1
286..287Voltage_AC_PhaseToPhase_120.1 V
288..289Voltage_AC_Phase_10.1 V
290..291Current_AC_Phase_1mA
292..293PowerReal_P_Phase_10.1 W
294..295PowerApparent_S_Phase_10.1 VA
296..297PowerReactive_Q_Phase_10.1 var
298..299PowerFactor_Phase_10.001
Phase 2
300..301Voltage_AC_PhaseToPhase_230.1 V
302..303Voltage_AC_Phase_20.1 V
304..305Current_AC_Phase_2mA
306..307PowerReal_P_Phase_20.1 W
308..309PowerApparent_S_Phase_20.1 VA
310..311PowerReactive_Q_Phase_20.1 var
312..313PowerFactor_Phase_20.001
Phase 3
314..315Voltage_AC_PhaseToPhase_310.1 V
316..317Voltage_AC_Phase_30.1 V
318..319Current_AC_Phase_3mA
320..321PowerReal_P_Phase_30.1 W
322..323PowerApparent_S_Phase_30.1 VA
324..325PowerReactive_Q_Phase_30.1 var
326..327PowerFactor_Phase_30.001

Read holding register for device ID 1 , Start address = 1024 Quantity = 16

Every 10 seconds

Every energy value is stored in four registers.
Example for EnergyReactive_VArAC_Sum_Produced:
For example the actual energy value is 463941 Wh. The kilowatt hours (463) are stored in register 1036..1037. The watt hours (941) are stored in register 1038..1039. To get the total energy in Wh multiply register 1036..1037 by 1000 and add register 1038..1039 to it.

Reg Description Unit
1024..1025EnergyReal_WAC_Plus_Absolute, EnergyReal_WAC_Sum_ConsumedkWh
1026..1027EnergyReal_WAC_Plus_Absolute, EnergyReal_WAC_Sum_ConsumedWh
1028..1029EnergyReactive_VArAC_Sum_Consumedkvarh
1030..1031EnergyReactive_VArAC_Sum_Consumedvarh
1032..1033EnergyReal_WAC_Minus_Absolute, EnergyReal_WAC_Sum_Produced kWh
1034..1035EnergyReal_WAC_Minus_Absolute, EnergyReal_WAC_Sum_Produced Wh
1036..1037EnergyReactive_VArAC_Sum_Producedkvarh
1038..1039EnergyReactive_VArAC_Sum_Producedvarh

Test conditions

Inverter

Fronius Symo GEN24 10.0 Plus
SW: 1.19.7-1 on 2023-02-28

Smart Meter

Fronius TS 65A-3